Edwards
®
2412 Two Zone
Fire Alarm Control Panel
Features
Field programmable initiating circuit
for non-verified or verified opera-
tion
Field programmable signal circuit for
non-silenceable or silenceable op-
eration
Form C alarm & trouble contacts
Alarm silence and trouble silence
switches
One person system walk test
Cabinet available in gray (2412) or
red (2412-R)
Batteries ordered separately
Description
The Edwards 2412, Two Zone Fire
Alarm Control Panel is designed for
use in buildings that require a super-
vised one or two zone fire alarm sys-
tem.
The microprocessor based 2412 is de-
signed for surface or flush mounting.
For normal operation the panel re-
quires batteries for standby power.
Batteries are charged by the panel's
built-in battery charger. See Fire
Alarm Control Panel Components,
page 12-11, for additional informa-
tion. The panel has three expansion
slots to accommodate optional equip-
ment. See System Design Criteria on
page 12-51.
Agency Approvals
UL Listed
CSFM Listed
Meets or exceeds UL 864
Meets or exceeds NFPA 72
Specifications
Two 2-wire Class B power limited
initiating circuits supports:
Waterflow alarm with or without
retard.
Connection of N.O. supervisory de-
vices with series resistor on same
circuit. Therefore, unnecessary to
assign a separate zone for supervi-
sory devices.
Two 2-wire Class B power limited
signal circuits support:
Continuous, 120 ppm, temporal
(3,3,3), California continuous (10 sec
on, 5 sec off), and California march
time (10 sec @ 120 ppm, 5 sec off)
Signal power: 2.5 amps/circuit, 4.0
amps for panel
Initiating circuit standby power:
1500 microamps/circuit
Auxiliary contact rating: 24V DC @
1 amp
Auxiliary power output: 24V DC
regulated @ 500mA
Battery lead supervision
Low/No AC power and battery de-
tection
Ground fault detection
High voltage transient protection
Optional Equipment
The following components are avail-
able for use with the 2412 panel.
See Fire Alarm Control Panel Compo-
nents, page 12-11, for details.
2400-DL Digital Alarm Communica-
tor Transmitter
2400-RCT Relay/City Tie Module
2400-2IDC Two Zone Expander
2400-BPA (Converts panel opera-
tion from Class B to Class A)
2400-IDCA (Converts expander
module from Class B to Class A)
Panel Operation
The panel has six modes of opera-
tion: normal, supervisory, alarm,
trouble, drill, and test mode. See Fire
Alarm Control Panel Operation, page
12-12, for details.
IMPORTANT
Certain jurisdictions require that Fire Alarm Systems, or components used therein, be installed, tested, certified,
serviced, or repaired by licensed personnel. Prior to Fire Alarm installation it is strongly recommended you contact the
local Fire Marshal with jurisdictional responsibility to determine all applicable code requirements.
Przeglądanie stron 0
1 2 3 4

Podsumowanie treści

Strona 1 - Fire Alarm Control Panel

Fire AlarmEquipmentClocksADA/HospitalSignalingDevicesTelephoneSignals &AccessoriesAppendix© 2000 EDWARDSCHESHIRE, CT 06410www.edwards-signals.com1

Strona 2 - Fax-on-Demand # 1162

Hazardous,NEMA &IP DefinitionsVisualSignalsBells &BuzzersElectronicSignalsProcessControlSignalsHorns &SirensMessageCenters &Annunciato

Strona 3 - Control Panel Components

Fire AlarmEquipmentClocksADA/HospitalSignalingDevicesTelephoneSignals &AccessoriesAppendix© 2000 EDWARDSCHESHIRE, CT 06410www.edwards-signals.com1

Strona 4 - Control Panel Operation

Hazardous,NEMA &IP DefinitionsVisualSignalsBells &BuzzersElectronicSignalsProcessControlSignalsHorns &SirensMessageCenters &Annunciato

Komentarze do niniejszej Instrukcji

Brak uwag