Edwards
®
2414 Four Zone
Fire Alarm Control Panel
Features
• Field programmable initiating cir-
cuit for non-verified or verified op-
eration
• Field programmable signal circuit
for non-silenceable or silenceable
operation
• Form C alarm & trouble contacts
• Alarm silence and trouble silence
switches
• One person system walk test
• Cabinet available in gray (2414) or
red (2414-R)
• Batteries ordered separately
Description
The Edwards 2414, Four Zone Fire
Alarm Control Panel is designed for
use in buildings that require a super-
vised four zone fire alarm system.
The microprocessor based 2414 is
designed for surface or flush mount-
ing. For normal operation the panel
requires batteries for standby power.
Batteries are charged by the panel's
built-in battery charger. See Fire
Alarm Control Panel Components,
page 12-11, for additional informa-
tion. The panel has two expansion
slots to accommodate optional equip-
ment. See System Design Criteria on
page 12-51.
Agency Approvals
• UL Listed
• CSFM Listed
• Meets or exceeds UL 864
• Meets or exceeds NFPA 72
Specifications
• Four 2-wire Class B power limited
initiating circuits support:
Waterflow alarm with or without
retard.
Connection of N.O. supervisory de-
vices with series resistor on same
circuit. Therefore, unnecessary to
assign a separate zone for supervi-
sory devices.
• Two 2-wire Class B power limited
signal circuits support:
Continuous, 120 ppm, temporal
(3,3,3), California continuous (10 sec
on, 5 sec off), and California march
time (10 sec @ 120 ppm, 5 sec off)
• Signal power: 2.5 amps/circuit, 4.0
amps for panel
• Initiating circuit standby power:
1500 microamps/circiut
• Auxiliary contact rating: 24V DC @
1 amp
• Auxiliary power output: 24V DC
regulated @ 500mA
• Battery lead supervision
• Low/No AC power and battery de-
tection
• Ground fault detection
• High voltage transient protection
Optional Equipment
The following components are avail-
able for use with the 2414 panel.
See Fire Alarm Control Panel Compo-
nents, page 12-11, for details.
• 2400-DL Digital Communicator
• 2400-RCT Relay/City Tie Module
• 4200-2IDC Two Zone Expander
• 2400-BPA (Converts panel opera-
tion from Class B to Class A)
• 2400-IDCA (Converts expander
module from Class B to Class A)
• 2400-ADM Annunciator Driver
Master
Panel Operation
The panel has six modes of opera-
tion: normal, supervisory, alarm,
trouble, drill, and test mode. See Fire
Alarm Control Panel Operation, page
12-12, for details.
Fax-on-Demand # 1169